ECM parameters

Every parameter in the ECM Explorer and the Existing Building Parameters panel, by tab.

On this page

How to read a row

Each row has up to three buttons:

  • Existing (gray) - Your building as calibrated.
  • Energy Code (blue) - What the selected energy code requires. Shown only where the code sets a value.
  • Customized (light blue) - The value you set. Select it, then move the slider.

Sliders that improve a building only go one way. For example, the roof R-value slider runs from the existing value up, and the lighting power slider from the existing value down. Values are shown with one decimal place.

A parameter appears only when it applies to your building’s systems. The conditions are listed in each table. If the building has a second HVAC zone, the Operations and Air-side tabs are split into (Main) and (Sub).

Envelope

The external walls, windows, roof and floor of the building. The info icon next to the heading shows the window-to-wall ratio (WWR).

ParameterWhat it isUnit or options
RoofEffective R-value of the roof insulationft²·h·°F/Btu, up to 60
Exterior WallsEffective R-value of the wall insulationft²·h·°F/Btu, up to 25
WindowsAssembly U-valueBtu/h·ft²·°F, down to 0.1
Window SC-valueShading coefficient of the windowsdown to 0.1
Window FilmAdd window filmAs-is, use
InfiltrationAir leakage during off-hoursCFM/ft², down to 0.2

Space Use

Lighting

ParameterWhat it isUnit or options
Interior LightingLighting power densityW/ft², down to 0.4
Lighting Control - During UnoccupiedShare of lighting turned off when unoccupied0 to 0.5 (0–50%)
Lighting Control - During OccupiedShare of lighting turned off when occupied0 to 0.5 (0–50%)

Plug loads

Energy codes don’t require plug load reductions, but buildings with high plug loads can save a lot here.

ParameterWhat it isUnit or options
Plug LoadPlug load densityW/ft², 0.1 to 1.2
Plug Load Control - During UnoccupiedShare of plug load turned off when unoccupied0 to 0.5 (0–50%)
Plug Load Control - During OccupiedShare of plug load turned off when occupied0 to 0.5 (0–50%)

Process loads

Loads that aren’t lighting, heating, ventilation, cooling or water heating, such as data equipment.

ParameterWhat it isUnit or options
Base LoadInternal heat gains from process equipmentkW, down to 0

Load profile charts

The Lighting Load Profile and Plug Load Profile charts show a 24-hour profile as a fraction of the peak, for weekdays (M–F), Sat and Sun. Choose Typical Operation or 24/7 Operation for buildings with floors running 24/7. The Existing line comes from the calibrated model. The Customized line follows your lighting or plug load density, the control reductions, and the HVAC startup and shutdown times on the Operations tab. The profiles themselves can’t be edited.

Operations

Operational measures don’t change the asset score, because the asset score uses typical operation schedules.

ParameterWhat it isUnit or optionsShown when
HVAC Startup - WeekdaysWhen the HVAC turns onMidnight to 8 amAlways (“24/7” if every floor runs 24/7)
HVAC Shutdown - WeekdaysWhen the HVAC turns offMidnight to 4 pmAlways
Days of OperationLast operating day of the week, from MondayFri, Sat, Sun, HolAlways
24/7 Conditioned FloorsAbove-ground floors running 24/7Number of floorsMain zone
Floors with Lights OffConditioned above-ground floors with the lights offNumber of floorsMain zone
Unconditioned FloorsAbove-ground floors that aren’t conditionedNumber of floorsMain zone
Unconditioned BasementsBelow-ground floors that aren’t conditionedNumber of floorsMain zone
Occupancy during Summer Break - Lighting and Plug LoadsWhether the building is occupied over the summeroccupied, unoccupiedUniversity buildings
Occupancy during Summer Break - Predominant HVACWhether the HVAC runs over the summeruse, offUniversity buildings
Cooling SetpointOccupied cooling temperature°F, 65 to 80Always
Heating SetpointOccupied heating temperature°F, 64 to 78Always
Cooling SetbackUnoccupied cooling temperature°F, 70 to 90Always
Heating SetbackUnoccupied heating temperature°F, 44 to 70Always
DOAS SchedulingWhen the dedicated outdoor-air unit runsoccupied, 24 hrsPTAC, PTHP, VRF, WSHP and fan coil systems

Air-side

The air distribution systems, usually a large share of the energy cost.

ParameterWhat it isUnit or optionsShown when
DX CoolingCooling efficiencyEER, up to 15DX cooling
Min Fan Operation - System LevelMinimum fan flow of the air handlerFraction, 0.2 to 1.0VAV systems
Min Airflow Ratio - Zone LevelMinimum flow of the VAV boxesFraction, 0.2 to 1.0VAV systems
DX CompressorCompressor speed controlone-spd, variableHeat pumps, VRF, WSHP
Heat Pump HeatingHeating efficiencyCOP, up to 4.5Heat pumps, VRF, WSHP
Furnace HeatingFurnace efficiencyFraction, up to 0.95Gas or oil furnaces
Cooling Supply AirSupply-air temperature in cooling°F, 54 to 59Zones with cooling
Heating Supply AirSupply-air temperature in heating°F, 90 to 120Zones with heating
Indoor Fan Operation - During OccupiedFan mode while occupiedintermittent, continuousAlways
Zone Fan Operation - During UnoccupiedFan behavior at nightcycle-on-first, stay-off, cycle-on-any, zone-fans-onlyAlways
Interior Fan SpeedSupply fan speed controlone-spd, two-spd, variable (VAV: one-spd, two-spd, optimized, captured)Always
Air-side Economizer - AvailabilityWhether an economizer is usedoff, useSystems with cooling: PSZ-AC, PSZ-HP, PVAV, VAV, SZ-CV-HW, SZ-CV-ER
Air-side Economizer - IntegratedWhether the economizer works together with coolingoff, useSame as above
Air-side Economizer - Drybulb High LimitOutdoor temperature above which the economizer stops°F, 50 to 75Same as above
Supply Air Temperature ResetReset of the supply-air temperatureoff, useVAV systems
Demand Control VentilationOutdoor air based on occupancyoff, useVAV systems
Motorized DamperOutdoor-air damper controluse, offAlways
Cooling Capacity OptimizationCooling capacity as % of existing%, 50 to 100Always
Heating Capacity OptimizationHeating capacity as % of existing%, 50 to 100Always
Minimum Outside AirOutdoor air as % of total airflow%, 10 to 40Always
Exhaust AirExhaust as % of total airflow%, 0 to 15Always

For VAV systems whose fan speed is captured, a chart compares the calibrated fan curve with the ASHRAE reference curve.

Water-side 1: chilled water plant

Shown when the building has a chiller plant, or a cooling tower for water-cooled DX or WSHP. The info icon shows the captured chiller capacity.

ParameterWhat it isUnit or optionsShown when
Chiller TypeCompressor typescrew, scroll, recip, centfglAir- or water-cooled chillers
Chiller Condenser TypeCondenser coolingair-cooled, water-cooledChillers without a water-side economizer
Water-side EconomizerFree cooling through the cooling toweroff, useWater-cooled chillers with a water-side economizer
Chiller PerformanceChiller efficiencykW/ton, down to 0.4Chillers
Chiller SizeCapacity as % of existing%, 50 to 120Chillers
Cooling Tower Fan ControlTower fan speed controlone-speed, two-spd, variableWater-cooled chillers, water-cooled DX, WSHP
Cooling Tower Pump HeadCondenser water pump headft, down to 10Same as above
Chilled Water Loop ConfigurationChilled water pumpingprimary-only constant, primary-only variable, primary/secondaryChillers
Primary CHW Pump Head, Secondary CHW Pump HeadPump heads of a primary/secondary loopft, down to 10Primary/secondary loops
Primary-only CHW Pump HeadPump head of a primary-only loopft, down to 10Primary-only loops
Chilled Water TemperatureChilled water supply temperature°F, 41 to 45Chillers
Chilled Water Snap ControlTurn chilled water off by outdoor temperatureoff, useChillers
Chilled Water Temperature ControlChilled water temperature resetfixed, OA reset, load resetChillers

Water-side 2: hot water plant

Shown when the building has a boiler or a hot water plant. The info icon shows the captured boiler capacity.

ParameterWhat it isUnit or options
Boiler TypeBoiler kindgas, cond (condensing), steam, elec
Boiler PerformanceThermal efficiency%, up to 99
Boiler SizeCapacity as % of existing%, 50 to 120
Hot Water PumpPump headft, down to 10
Hot Water LoopHot water supply temperature°F, 125 to 185
Hot Water Snap ControlTurn hot water off by outdoor temperatureoff, use
HW (CHW) SnapOutdoor temperature for the snap control°F, 45 to 70
Hot Water Temperature ResetHot water temperature resetfixed, OA reset, load reset

Water Heater

Shown when the building has a domestic water heater. Savings are based on the captured occupancy schedule, the water heater capacity and, for gas water heaters, the gas use.

ParameterWhat it isUnit or options
Water Heater TypeFuel or technologygas, elec, heat pump
Water Heater PerformanceEfficiency% (EF or Et) or COP. Code values: gas 80, electric 96, heat pump 3.6
Peak DemandHot water demandGPM

Solar PV

Generation is based on monocrystalline panels with 21% efficiency.

ParameterWhat it isUnit or options
Solar PV capacityInverter sizekW, 0 to 999
Mount TiltPanel tilt angledegrees, 20 to 65. The blue button suggests a tilt based on the building’s latitude.

Electrification

Shown when the building heats with gas or fuel oil. These options replace the heating system chosen on the other tabs, for an electrification study.

Space Heating Source is a list: As-Built/Existing, Electric Resistance, Air-source Heat Pump, Electric Boiler and Variable Refrigerant Flow (VRF). Options that don’t fit the building’s air distribution are grayed out. The heat pump is modeled at 3.0 COP, and VRF at 11 EER and 3.3 COP. The rest of the existing system is assumed to stay as it is: for example, a gas furnace in a rooftop unit can be replaced with electric resistance heat or a heat pump.